When a barrel zone on an injection moulding machine will not reach or hold its set temperature, the cause is usually one of four things: a failed heater band, a faulty thermocouple, a failed fuse or trip, or a problem in the wiring or the controller output that switches the heater. The zone readings on the controller usually point to which one, and a qualified engineer can confirm it with a few electrical tests.
Safety first. Heater bands run at mains voltage and the barrel stays extremely hot long after the machine stops. Leave covers in place and do not touch heaters, thermocouples or terminals. A machine has to be live while it is tested electrically, so testing should only be carried out by a competent person. If the machine is left unattended, it should be isolated and locked off. Heater bands and thermocouples should only be replaced with the machine isolated and locked off.
How the barrel heating works
The barrel is divided into heating zones from the feed throat to the nozzle. Each zone has one or more heater bands clamped around the barrel and a thermocouple that measures the temperature. The controller compares that reading with the set point and switches the heaters on and off, usually through a contactor or a solid state relay, to hold the zone at temperature.
If any part of that loop fails, the zone either cannot heat, cannot be measured correctly, or cannot be controlled.
Common symptoms and what they usually mean
| What you see | Likely cause |
|---|---|
| One zone stays cold while the others heat up | Failed heater band, a failed fuse or trip, a loose or burnt connection, or a fault in that zone’s output |
| Zone heats very slowly or cannot quite reach set point | One of two or more bands in the zone has failed, or a band is loose on the barrel |
| Thermocouple or sensor break alarm | Broken thermocouple, damaged lead or a loose connection at the terminal |
| Reading jumps around or reads clearly wrong | Damaged thermocouple, the wrong thermocouple type, or a thermocouple not seated properly in its pocket |
| Zone overshoots and keeps getting hotter | Output stuck on, such as a welded contactor or failed solid state relay. Treat this as urgent |
| Short shots, splay or burnt material with no change to the mould or material | Melt temperature is not what the controller says, often from a misreading thermocouple |
Heater band faults
Heater bands fail through age, through physical damage, and most often through poor contact with the barrel. A band that is not clamped tightly runs hotter inside than it should, because the heat cannot escape into the barrel, and its element burns out early. Material leaking from the nozzle or barrel end can also find its way under a band or into its terminals.
An engineer will check the band’s resistance against its rated value, check the insulation to earth, and inspect the terminals and wiring. A band reading open circuit has failed and needs replacing.
Thermocouple faults
A thermocouple can break, be damaged at the lead, or work loose so its tip no longer touches the bottom of its pocket. A loose thermocouple reads low, so the controller keeps heating and the real temperature runs above set point. Fitting the wrong type, for example a type K thermocouple on a controller set up for type J, gives a reading that looks plausible but is wrong.
Because the controller can only control what it measures, a thermocouple fault can cause processing problems long before it causes an alarm.
What your team can safely check
- Note which zone is affected, its set point and its actual reading, and any alarm message.
- Watch how the zone behaves after switching on: does it not heat at all, heat slowly, or overshoot?
- Look, without touching, for obvious signs such as material leaking around the barrel, burnt wiring or a displaced cover.
- Check whether the fault started after any work on the barrel, such as a nozzle or screw change.
That information lets an engineer arrive knowing which part is likely to be needed.
Preventing heating faults
- Make sure heater bands are clamped firmly to a clean barrel surface, and check them after any work on the barrel.
- Keep the barrel and nozzle area clean so leaking material cannot reach bands and terminals.
- Make sure thermocouples are the correct type and fully seated in their pockets.
- Have heater band and thermocouple readings checked across all zones as part of a regular service.
- Keep spare bands and thermocouples for the zones that fail most often on your machines.
Heater bands from Immpress
For Boy machines, the heater bands we supply are made in Germany and, although they do not show the Boy mark, they are identical to the originals. For Manumold machines, the original heater bands were unsuitable for modern moulding machines, so we have had them re-manufactured to give better control over temperatures. See our spare parts page or send us your request.
Heater band questions
Why will one barrel zone not heat up on my injection moulding machine?
The most common causes are a failed heater band, a failed fuse or trip, a loose or burnt connection, or a fault in the output that switches that zone, such as a contactor or solid state relay. An engineer can confirm which with a resistance check and an inspection of the wiring.
How do I know if it is the heater band or the thermocouple?
A cold zone with a sensible reading usually points to the heater or its supply. A sensor break alarm, or a reading that jumps around or is clearly wrong, usually points to the thermocouple or its lead.
Why do heater bands burn out early?
The most common reason is poor contact with the barrel. A loose band cannot pass its heat into the barrel, runs too hot and fails early. Leaking material and damaged terminals are other common causes.
Can you supply heater bands for Boy and Manumold machines?
Yes. Immpress supplies Boy heater bands made in Germany that are identical to the originals, and re-manufactured Manumold heater bands that give better control over temperatures.